TRS-01a
The ambient temperature transducer is a basic device of the TRS System. It is designed particularly to measure temperature in rooms where food products are manufactured and stored. It has a small plastic casing. It measures temperature within the range of -40°C to +85°C.
Parameters
Power supply | typ. 10V DC (9V DC ÷ 12V DC) |
---|---|
Power consumption | 4,2 mA; during Modbus transmission: do 60 mA |
Input | temp. sensor: semiconductor integrated circuit; measurement range -40°C ÷ +85°C; measurement error within th range -10°C ÷ +50°C: ±0,5°C |
Communication interface | RS-485 / Modbus RTU |
Storage temperature | -40°C ÷ +85°C |
Operating temperature | -40°C ÷ +85°C |
Case dimensions | 63 x 58 x 35 mm |
Protection class | IP 65 (case), IP 30 (sensor) |
Connection cable | 4 conductors (2 supply conductors + 2 data transmission conductors) |
Mounting | to wall, 2 M3 bolts |
Transmission parameters | 9600 bit/sek. |
Number of modules in 1 network | max. 127 |