SIAi-8

Module SIAi-8 allows to measure analog values from 8 current (or voltage) inputs via the RS-485 connection, with speed rate about 10 Hz (every channel). Measurement results can be internally recalculated due to one of available characteristics: linear, square or user definable multipoint (max. 20 points length). It finds application in distributed control and visualization systems.

Parameters

Power supply typ. 24V DC (16V DC ÷ 30V DC)
Current consumption typ. 20 mA
Humidity max. 90%, non-condensing
Input SIAi-8P: 8 x current 0-20 mA; 4-20 mA; SIAi-8N: 8 x voltage 0-10 V; 2-10 V; 0-5 V; 1-5 V
Communication interface RS-485 / Modbus RTU
Breakdown voltage all 8 inputs are galvanically isolated from module supply and RS-485 interfac
Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (with option 08)
Data memory non-volatile memory, EEPROM type
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Case dimensions 101 x 22,5 x 80 mm
Protection class IP 20 (housing and connection clips)
External fuse T – type, max. 1 A (required)
Number of modules in 1 network max. 128
Mounting on the 35 mm strip
Transmission parameters 1200 ÷ 115200 bit/s.