QM-211
ProSens is a new line of modern industrial devices, which integrates sensors, converters, meters and controllers functionalities. Using the latest miniaturisation technologies these compact devices are able to be equipped with one independent universal input, two binary or two analogue outputs, as well as communication port RS-485 with Modbus protocol.
Model QM-211 has integrated radial temperature or temperature and humidity probe, Ø 18 mm, L=40 mm,
PTFE filter cap.
A large built-in display and output signals mean that the ProSens line units find applications in control systems. There are many industrial applications, where ProSens can act as stand-alone controller. It can also cooperate with master devices via Modbus protocol, being part of big network, which makes it perfect device for distributed monitoring system.
Parameters
Power supply | 24V DC (11 ÷ 36V DC); for versions with voltage output min. 16V DC |
---|---|
Power consumption | max. 2,5 W |
Type of probe | integrated radial, length 40 mm, Ø 18 mm, stainless steel 316L, PTFE filter cap |
Probe parameters | temperature sensor: measuring range: -30 ÷ 80°C (typ.err. ±0,5°C @ -10 ÷ 80°C) or temperature and humidity sensor: measuring temperature range: -30 ÷ 80°C (typ.err. ±0.2°C @ 10 ÷ 60°C; 0.4°C @ -30°C; 0.7°C @ 120°C); measuring humidity range: 0 ÷ 100% RH (typ.err. ±1.8% RH; 10÷90% @ 25°C) |
Inputs | 0 or 1 universal: current; voltage; thermocouple K, S, J, T, N, R, B, E types |
Measurement range | current: 0/4-20 mA; voltage: 0/1-5 V, 0/2-10V, 0-60 mV, 0-75 mV, 0-100 mV, 0-150 mV; RTD: Pt100, Pt500, Pt1000, measuring range: -100°C ÷ 600°C; thermocouple: type K, S, J, T, N, R, B, E; measuring ranges: -200°C ÷ +1370°C (K); -50°C ÷ +1768°C (S); -210°C ÷ +1200°C (J); -200°C ÷ +400°C (T); -200°C ÷ +1300°C (N); -50°C ÷ +1768°C (R); +250°C ÷ +1820°C (B); -200°C ÷ +1000°C (E) |
Binary outputs | 0, 1 or 2 electronic NO relays, 24V AC/35V DC, max. 200 mA |
Analogue outputs | 0, 1 or 2: active current: operating range 0/4-20 mA (0-24 mA max.); passive current: isolated, operating range 4-20 mA (2.8-24 mA max.); active voltage: operating range 0/1-5V, 0/2-10V (0-11V max.) |
Communication interface | RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU, not galvanically isolated |
Operating temperature | -30°C ÷ +80°C, case with electronics (out of range -20 ÷ +70°C LCD and IR receiver turn off) |
Accuracy | 0.1% @25°C ± one digit (inputs: current, voltage, milivoltage, thermoresistance, thermocouple K, J, E); 0.2%@ 25°C (thermocouple N), 0.5%@25°C (thermocouple S, T, R, B) |
Case material | ASA LURAN |
Case | wall mounted |
Case dimensions | 120 x 90 x 50 mm |
Protection class | IP 67 (version without display); IP 65 (version with display) |
Display | optionally: graphic LCD, 128 x 64 points, with backlight |
Temperature stability | typ. 50 ppm/°C |