MultiLog SRD-99-4328

Categorías: ,

The SRD-99 device is designed to record and display current values as well as to present technological parameters in the form of graphs. The device is equipped with 4 RTD inputs, one pulse (digital) input for controlling the recording process and one USB Host port for flash data storage. Internal memory has 2 MB capacity (0.5 million data recordings altogether) or 8 MB in version with USB port (2 milions data recordings).

Parameters

Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Outputs 2 electronic relays (ER1, ER2) with max. load 24V AC (35V DC) / 200 mA; sensors supply (only current version): 24 V DC ± 5%, max. 200 mA, not separated from measuring inputs
Measurement range -100,0°C ÷ +600,0°C with resolution 0,1°C; -148,0°F ÷ +999,9°F with resolution 0,1°F
Power consumption typical 7 VA; max. 12 VA
Input 4 x Pt 100/500/1000; 1 digital input 24V DC, optocoupled
Communication interface RS-485 / Modbus RTU or USB Host port
Transmission parameters 1200 – 115200 bit/sek.
Internal memory capacity 2 MB in version without USB, 8 MB in version with USB Host port
Data recording period 1 s / 2 s / 5 s / 10 s / 15 s / 20 s / 30 s / 1 min / 2 min / 5 min / 10 min / 15 min / 20 min / 30 min / 60 min
Storage temperature -10°C ÷ +70°C
Operating temperature 0°C ÷ +50°C
Accuracy 0,1% @25°C
Case dimensions 96 x 96 x 100 mm
Case panel mounting
Case material NORYL – GFN2S E1
Protection class version without USB: IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-99; version with USB: IP 40 or IP 54 (when fitted with STD-99 transparent door)
Display graphic LCD, 128 x 64 points, with backlight
Panel cut-out dimensions 90,5 x 90,5 mm
Software Free Loggy Soft and S-toolkit software for data recorder can be downloading directly from section „Download”
Installation depth min. 102 mm