SWP-99

Categories: ,

The SWP-99 indicator is intended for measuring and presentation of current values from 8 measuring channels. Each channel can be individually designated (described) with any measuring unit. The LCD graphical display allows for visualization of the values from all 8 channels simultaneously. A significant advantage is possibility of viewing the trends in each measuring channel as the graphs for the last 12 seconds or about 1,5 minutes. Device is equipped in electronic relay outputs that can be used to control external devices. There are icons on the screen signalling the status of the outputs.

The device supports S-Toolkit software  free in «Download» section.

Parameters

Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Outputs 2 electronic relays, NO type (ER1, ER2) with max. load 24V AC (35V DC) / 200 mA, overload protection
Measurement range ± 9999 + decimal point
Power consumption typical 7 VA; max. 12 VA
Input 2, 4 or 8 inputs 0/4-20 mA, common earthing
Stability typ. 50 ppm/°C
Communication interface RS-485, 8N1 and 8N2, 1200 bit/s ÷ 115200 bit/s, Modbus RTU (isolated from measuring inputs)
Storage temperature -10°C ÷ +70°C
Operating temperature 0°C ÷ +50°C
Accuracy ± 0,25% ± one digit in the entire operation range
Case material NORYL- GFN2S E1
Case dimensions 96 x 96 x 100 mm
Case panel mounting
Protection class IP 65 (front), available options: additional frame IP 65 for panel cut-out sealing, transparent door STD-99; IP 20 (case and connection clips)
Panel cut-out dimensions 90,5 x 90,5 mm
Display with backlighting, graphic LCD, 128 x 64 points
Software The device supports S-Toolkit software – free in «Download» section.
Installation depth min 102 mm