SLIK-94

The device has two independent counting inputs that can operate in various configurations. A programmable function input enables changing the operating mode of the counting inputs (up-down and down-up or quadrature) or stopping the count. The SLIK-94 counter features an independent reset input. It has 0, 2 or 4 relay (or OC) outputs with programmable activation thresholds, which can be used to control external equipment.

Parameters

Power supply 19V ÷ 50V DC; 16V ÷ 35V AC or 85 ÷ 260V AC/DC
Measurement range -99999 ÷ 999999
Power consumption for 85 ÷ 260V AC/DC and 16V ÷ 35V AC power supply: max. 4,5 VA; 19V ÷ 50V DC power supply: max. 4,5 W
Inputs pulse, 2 x counting; 1 x programmable, 1 x reset
Counting mode adding, subtracting or quadrature
Data memory non-volatile memory, EEPROM type
Input levels low: 0 V ÷ 1 V; high: 10 V ÷ 30 V
Input frequency electronic: 10 kHz / 5 kHz (for quadrature); contact: max. 90 Hz (adjustable filter)
Communication interface RS-485, 1200 ÷ 115200 bit/s, 8N1 and 8N2, Modbus RTU
Output 0, 2 or 4; relay 1A/250V AC (cosφ=1) or OC 30mA/30VDC/100mW; power supply output: 24V DC +5%, -10% / max. 100 mA
Storage temperature -10°C ÷ +70°C or -20°C ÷ +70°C (depending on version)
Operating temperature 0°C ÷ +50°C (standard), -20°C ÷ +50°C (option)
Reset reset: button and electric, with keylock
Case panel mounting
Case material NORYL-GFN2S E1
Case dimensions 96 x 48 x 100 mm
Protection class IP 65 (front), available additional frame IP 65 for panel cut-out sealing; IP 20 (case and connection clips)
Panel cut-out dimensions 90,5 x 43 mm
Display LED, red (green on request), 6 x 13 mm high
Installation depth min 102 mm
Typical applications Measuring the length of the material being wound, featuring control of the cutting knife drive system according to set parameters, control of the material drive system, as well as alarm signalling.